The essentials in 60 seconds
- Loads first, hardware second. Write down what has to keep running during an outage, how many watts it draws and for how long. Without that list you end up buying too big, too small or the wrong thing.
- Power (W) and energy (Wh) are different things. Power decides whether a device starts at all, energy decides how long it runs. Motors (pumps, fridges, freezers, compressors) draw several times their rated power at start-up.
- UPS = no interruption, but only minutes to a few hours, for IT. Power station = portable battery for individual devices, hours up to a day. Generator = as long as there is fuel, but noise, exhaust and maintenance. Home battery = quiet and convenient, but only if it is explicitly installed for island (backup) mode.
- Many home batteries deliver nothing during a power cut. Without a backup box, transfer equipment or backup function, a grid-tied inverter shuts down when the grid fails, even with a full battery.
- A generator is never fed into the house wiring through a socket. Connecting to the house installation is only done through a changeover switch (grid–0–generator) fitted by an authorised electrician (behörig elinstallatör). Backfeeding endangers line workers, and carbon monoxide kills people every year: generators belong outdoors.
- An outage of 12 hours or more entitles you to statutory compensation (avbrottsersättning) in Sweden, and outages longer than 24 hours are in principle not allowed for the network operator. Still, plan for several days.
This article is part of the series on power cuts in Sweden. The overview of all topics – including heating, water, medical devices, animals and a decision guide per household – is in the complete guide to power cuts in Sweden.
Contents
- Four questions before you buy anything
- How long do power cuts last in Sweden?
- Power, energy, starting current: the basics
- Typical loads during an outage
- Working out runtime, step by step
- Batteries: LFP, NMC, lead-acid, cold
- Sine wave quality: why it matters
- UPS: types and transfer times
- Portable power station
- Your electric car as a power source
- Generators: sizes, fuel, carbon monoxide, connection
- Home battery: island mode or grid-tied only?
- From my own installation
- All options compared
- Decision tree by scenario
- Winter in Norrland
- Costs at market prices
- Rules in Sweden
- Maintenance: making sure it works when needed
- Common mistakes
- Printable checklist
Four questions before you buy anything
Backup power is often approached from the hardware side: “I’ll buy a generator” or “the battery will handle it”. It works better the other way round. Four questions decide which solution fits:
- What has to keep running? Not “the house”, but a concrete list: heating (and whatever the heating needs to run), water (well pump, pressure pump), fridge and freezer, router and phone, lighting, alarm system; with animals, ventilation, drinking water and milking; in a business, till, server and refrigeration.
- For how long? An hour, a day or a week? The answer separates battery solutions from fuel-based ones.
- How fast must it switch over? A computer, a heating controller or a medical device cannot tolerate an interruption. A fridge copes with an hour without power without any trouble.
- How does the power reach the devices? With an extension lead straight to the device, through a backup socket, or through a permanently installed changeover switch in the consumer unit? Anything that touches the fixed wiring is, in Sweden, work for an authorised electrician.
Once you have answered these four questions, you have made 80 % of the decision. The rest of this guide provides the numbers.
How long do power cuts last in Sweden?
The good news first: the Swedish grid is reliable. According to the Swedish Energy Markets Inspectorate (Ei), unannounced outages on local distribution networks in 2024 averaged around 63 minutes per customer per year, with roughly one outage per customer. 2024 was a quiet year without major storms, and still just over 6,450 customers were without power for more than 24 hours.
The bad news: averages do not help if you live at the end of a long overhead line through the forest. Storm Gudrun left around 730,000 customers without power in January 2005, and the longest outage lasted 45 days. Since 2011, network operators must ensure that outages never exceed 24 hours (Electricity Act, chapter 4, section 20), unless the cause is outside their control and could not reasonably have been foreseen or avoided. Severe storms, ice loading and snow-laden trees are exactly that kind of cause.
Compensation for long outages (avbrottsersättning)
If the supply is interrupted on one or more phases for at least twelve consecutive hours, the network operator pays compensation automatically, no later than six months afterwards, usually as a credit on your network bill. An outage only counts as over once power has then been on without interruption for two hours.
| Length of outage | Compensation (share of annual network charges) |
|---|---|
| 12 to 24 hours | 12.5 %, at least 2 % of the price base amount (around SEK 1,200 in 2026) |
| each further 24-hour period started | + 25 % |
| cap | 300 % of annual network charges |
Example: with network charges of SEK 8,000 a year, a 36-hour outage brings 12.5 % + 25 % = 37.5 %, i.e. SEK 3,000. That is compensation, not a replacement for a thawed freezer or a frozen basement; you can claim damages for those separately. As of October 2026 this is governed by the Electricity Act (1997:857). On 1 January 2027 it will be replaced by the new Electricity Market Act (2026:1281), so check whether details have changed.
What this means for planning
I plan backup power in three tiers:
- Tier 1: seconds up to an hour. The normal case. The main point is that nothing crashes: router, computer, heating controller, alarm. Tool: UPS, or a power station with UPS function.
- Tier 2: up to about 24 hours. A storm, a line down in the forest. Fridge and freezer, water, light and communications should keep going. Tools: power station, home battery with island mode, small generator.
- Tier 3: several days. A major winter disruption. Now it is about heat and water. Tools: generator with fuel reserve, home battery plus recharging (solar, generator), wood stove as a heat source that needs no electricity.
Power, energy, starting current: the basics
Three concepts are enough to understand any backup solution.
Power in watts (W): can the source carry it?
Power is what a device draws at this moment. A kettle draws 2,000 W, a router 10 W. Every backup source has a maximum power, and if it is exceeded, it shuts down. What counts is the total of everything running at the same time.
Energy in watt-hours (Wh, kWh): how long will it last?
Energy is power multiplied by time. A 10 W router uses 240 Wh in 24 hours. A 1,000 Wh battery could in theory run it for just over four days, in practice less (see below). Battery energy is often given in amp-hours (Ah). Conversion: Wh = volts × Ah. A 12 V battery with 100 Ah stores 1,200 Wh, a 48 V battery with 100 Ah stores 4,800 Wh.
Watts or volt-amperes (VA)?
UPS units and generators are often rated in VA or kVA. With motors and power supplies, part of the current flows without doing work (reactive power). The usable real power in watts is therefore usually lower than the VA figure, typically 0.6 to 0.9 times; for generators a factor of 0.8 is commonly used. A 5 kVA generator then delivers about 4 kW. Datasheets usually give both; calculate in watts.
Starting current: the underestimated peak
Electric motors draw several times their running current when they start, two to seven times depending on the motor, for a fraction of a second up to a few seconds. This affects anything with a compressor or pump: fridge, freezer, well pump, pressure pump, fixed-speed heat pump, milking equipment, fan motors. A backup source that only covers running power will not start these devices, or it manages the first start and fails the next time the compressor kicks in.
Modern variable-speed devices (inverter heat pumps, circulation pumps with EC motors, inverter fridges) start softly and are much more forgiving. You will find the exact figure on the rating plate or in the installation manual under terms such as startström (Swedish), LRA (locked rotor amps) or inrush current.
Typical loads during an outage
The values below are orders of magnitude. What counts is always your own device: read the rating plate or, better, measure it with a plug-in energy meter or a smart plug with power monitoring.
| Load | Running power | Start-up | Energy per day |
|---|---|---|---|
| Fibre box (ONT) + router | 10–25 W | none | 0.25–0.6 kWh |
| 4G/5G router | 5–10 W | none | 0.1–0.25 kWh |
| PoE camera | 4–8 W | none | 0.1–0.2 kWh |
| LED lamp | 5–10 W | none | depends on use |
| Charging a laptop | 30–65 W | none | 0.1–0.3 kWh |
| Fridge / fridge-freezer | cycles, 50–150 W when running | high (compressor) | 0.3–1.0 kWh |
| Chest freezer | cycles, 50–150 W when running | high (compressor) | 0.4–1.0 kWh |
| Heating circulation pump (EC motor) | 4–45 W | low | 0.1–1 kWh |
| Well pump / pressure pump | 0.5–1.2 kW, briefly | very high (2–3 times or more) | depends on water use |
| Heat pump (compressor) | several kW | low with inverter, otherwise high | many kWh in winter |
| Immersion heater in the heat pump | 3–9 kW | none | a lot in winter |
| Kettle, hob | 1.5–2.5 kW | none | short bursts |
Sources for the guide values: fridges and freezers from consumer tests (annual consumption of modern fridge-freezers roughly 114–365 kWh, i.e. 0.3–1.0 kWh a day), circulation pump from the manufacturer (Grundfos Alpha1 GO: 4–45 W), immersion heater from the datasheet (NIBE F1255: 6.5 and 7 kW), start-up values from generator sizing guides (US-size fridge about 700 W running and 2,200 W starting, well pump about 1,000 W and 2,800 W). Router and camera figures as in the guide to cameras in a holiday home without broadband.
Heating is almost always the sticking point. A heat pump with its immersion heater needs so much power in winter that it can hardly be run from batteries and not at all from small generators. But oil, pellet and district heating also need electricity: for the burner, controls and circulation pump. Without power, you are left with whatever heats without power: wood stove, tiled stove, gas or paraffin heater (the latter carry a carbon monoxide risk and should only be used indoors if the manufacturer allows it).
Working out runtime, step by step
The basic formula is simple. It only becomes honest once the losses are included:
Runtime (h) = usable energy (Wh) × efficiency ÷ (load + idle consumption) (W)
Step 1: usable energy
Not all of the nominal capacity is usable. Lithium iron phosphate (LFP) batteries can be discharged to about 90–100 %; lead-acid batteries should only be discharged to about half for the sake of their lifespan. Home batteries also have a configured reserve.
Step 2: inverter losses
The battery supplies direct current; the fridge needs 230 V alternating current. The inverter in between typically loses 5–15 %, often more at low load. I calculate with 85–90 %.
Step 3: idle consumption
This is the most frequently forgotten number. Every inverter draws power as soon as it is on, even with no load. With small power stations this is often a few watts to a few tens of watts. My own off-grid-type inverter draws around 126 W, around the clock. Modern home batteries measure between 4 and 64 W according to tests by HTW Berlin. With small loads, idle consumption eats a large part of the battery.
Step 4: average load, not peak load
For runtime, the average load over the day is what matters. A fridge drawing 100 W but running only a quarter of the time uses 25 W on average. That is why you calculate kWh per day ÷ 24.
Worked example: a cabin in winter with a power station
A 1,024 Wh power station (LFP) is meant to run a fridge, a 4G router, two cameras and some lighting in a cabin.
| Step | Calculation | Result |
|---|---|---|
| Usable energy | 1,024 Wh × 90 % | 920 Wh |
| after inverter losses | 920 Wh × 88 % | 810 Wh |
| Fridge | 0.5 kWh/day | 500 Wh |
| 4G router | 10 W × 24 h | 240 Wh |
| 2 cameras | 2 × 6 W × 24 h | 290 Wh |
| LED lighting | 20 W × 5 h | 100 Wh |
| Inverter idle (assumption) | 15 W × 24 h | 360 Wh |
| Total per day | 1,490 Wh | |
| Runtime | 810 ÷ 1,490 × 24 h | about 13 hours |
Without the fridge it is 810 ÷ 990 × 24 ≈ 20 hours. If the router and cameras run from the power station’s 12 V outputs instead of through the 230 V inverter, most of the idle and conversion losses disappear and runtime rises noticeably. The lesson: a power station of around 1 kWh gets you through a night, not a week. For longer you need recharging (solar panel, generator, car) or more capacity.
Worked example: how big a generator does a house need?
A house with its own well and a pellet boiler should run heating, water, fridge, freezer and communications during an outage. The heat pump is not run in backup mode.
| Step | Value |
|---|---|
| Boiler with controls and circulation pump (rating plate, assumption) | 400 W |
| Fridge + freezer when both run | 300 W |
| Router, lighting, charging | 200 W |
| Well pump running | 1,000 W |
| Running load with everything on at once | 1,900 W |
| Allowance for the largest start-up: well pump 2,800 W instead of 1,000 W | + 1,800 W |
| Peak demand | 3,700 W |
| Margin of 20–25 % for ageing, cold, measurement error | about 4.5 kW |
A 2 kW inverter generator is not enough here. A generator of about 5 kW (5.5–6 kVA) carries the load. A trick that often saves a size class: not everything at once. If you only run the well pump when the fridge and freezer are not starting, or have your electrician fit load shedding, you can manage with less.
Batteries: LFP, NMC, lead-acid, cold
LFP (lithium iron phosphate)
Now the standard in power stations and home batteries: thousands of cycles, thermally stable, high usable capacity and almost no capacity loss at high discharge currents. Drawback: lower energy density, so heavier per kWh.
NMC (lithium nickel manganese cobalt)
Higher energy density, hence common in older or very light power stations and in many electric cars. Fewer cycles than LFP and more sensitive to overheating. For a device that sits in a cupboard for years waiting for an emergency, LFP is usually the better choice.
Lead-acid (AGM, gel, flooded)
Cheap, heavy, and found in nearly every small UPS. Two quirks are worth knowing. First, lead-acid should only be discharged to about half, otherwise its life drops sharply. Second, the Peukert effect: a lead-acid battery’s rated capacity usually refers to a 20-hour discharge (C20). Discharged faster, say in two hours, it delivers considerably fewer amp-hours. LFP hardly shows this effect. A 100 Ah lead-acid battery and a 100 Ah LFP battery are therefore not equivalent in backup use: the LFP battery often delivers almost twice the usable energy.
Cold: the Norrland problem
- Lithium batteries must not be charged below 0 °C. Charging in sub-zero temperatures causes lithium deposits on the anode that permanently damage the battery and, at worst, cause internal short circuits. Manufacturers recommend charging roughly between +5 and +45 °C. Good devices block charging in the cold themselves; some heat the battery first.
- Discharging works in the cold, but available capacity and power drop. A power station in an unheated shed at −20 °C delivers noticeably less than one in the living room.
- Lead-acid batteries also lose capacity in the cold, and a discharged lead-acid battery can freeze.
- In practice: store and operate batteries frost-free. A power station for the cabin belongs inside the house, not in the car or the shed. My own battery is installed frost-free.
Sine wave quality: why it matters
The grid supplies a clean sine wave at 230 V and 50 Hz. Backup sources generate their own voltage, and not all do it equally well:
- Pure sine wave: online UPS, good power stations, inverter generators, home battery inverters. Everything that runs on the grid runs on these.
- Modified sine / stepped wave: cheap inverters and some offline UPS units on battery. Computer power supplies usually cope for a short time. Motors run hotter and noisier, some power supplies with power factor correction shut down, and heating controllers and circulation pumps with electronics may throw errors.
- Conventional generators (without inverter): the voltage comes straight from the alternator. With changing loads, voltage and frequency fluctuate and the waveform is less clean. Fine for tools, fan heaters and robust motors, borderline for electronics.
- Inverter generators first produce direct current and then, through an inverter, a stable sine wave. They are quieter, more economical at part load and suitable for electronics, but cost more per kW.
Rule of thumb: anything with electronics (heating controls, heat pump, computers, routers, modern fridges, medical devices) should run on a pure sine wave.
UPS: types and transfer times
A UPS (uninterruptible power supply) bridges outages so quickly that connected devices notice nothing, but only for a short time. The IEC 62040-3 standard distinguishes three designs:
| Type | How it works | Transfer time | Output on battery | Use |
|---|---|---|---|---|
| Offline / standby (VFD) | Mains passes through; on failure a relay switches to battery | about 4–20 ms | often modified sine | router, simple PC |
| Line-interactive (VI) | like offline, but also evens out voltage fluctuations without the battery | about 2–6 ms | sine or stepped, depending on model | router, NAS, home office |
| Online / double conversion (VFI) | Loads always run from the inverter; mains only charges | 0 ms | pure sine, distortion under 3 % | servers, heating controls, sensitive equipment, running behind a generator |
Most computer power supplies ride through 10–20 ms on their own, so a line-interactive UPS is almost always enough for routers and PCs. An online UPS makes sense when devices genuinely cannot tolerate an interruption, or when the UPS sits behind a conventional generator: it turns the generator’s rough output back into a clean sine wave.
Limits: small UPS units have batteries of a few hundred watt-hours. That is enough for several hours of router and fibre box, but not for a fridge. Fridges, freezers and pumps do not belong on a small UPS; their starting current overloads it. Lead-acid batteries in a UPS age even when unused and normally need replacing after a few years. Run times for router, cameras and phone are worked out step by step in Power cut: how long do router, cameras and phone keep running?
Portable power station
A power station is a portable lithium battery with a built-in inverter, charge controller and sockets. Common sizes range from 250 Wh to over 3 kWh, and some can be expanded with extra batteries.
What to look for
- Continuous and surge power: a model rated 1,800 W continuous and 3,600 W surge will start a fridge, but not a kettle and a fridge together.
- Cell chemistry: prefer LFP (a common 1,024 Wh model is rated at 4,000 cycles to 80 % remaining capacity).
- UPS function: many units switch over in under 10–30 ms. That is fast, but not a certified online UPS. Usually fine for computers; test sensitive equipment first.
- Idle consumption of the inverter (see the worked example) and whether it can be switched off when only the 12 V or USB outputs are needed.
- Charging: from the mains, a solar panel, the car or a generator. To bridge longer outages, you need a way to recharge.
- Temperature range for charging and operation according to the datasheet.
How the power reaches your devices
The simple and safe way: plug devices straight into the power station with an extension lead. Some manufacturers also sell transfer panels for individual circuits. These touch the fixed wiring and may only be installed by an authorised electrician. Never feed a power station into a wall socket with a lead that has a plug on both ends. That makes the pins of the other plug live, can backfeed the grid and is potentially lethal.
Your electric car as a power source
An electric car has a large battery. Some models can supply 230 V through an adapter in the charging port or a socket in the cabin (vehicle-to-load, V2L), on common models up to about 3.6 kW, with automatic cut-off at low charge. That is enough to run a fridge, freezer, lighting and router through extension leads for many hours, like a very large power station.
Powering the house from the car (vehicle-to-home, V2H) needs a bidirectional charger, isolation from the grid and approval from the car maker. In Sweden that is still the exception. If you are planning it, treat it like a home battery with island mode: electrician, network operator, transfer equipment.
Generators: sizes, fuel, carbon monoxide, connection
A generator (Swedish elverk or reservelverk) is the only solution that runs practically indefinitely, as long as there is fuel. In return it is noisy, produces exhaust and needs looking after.
Size classes
| Class | Typical power | Design | For |
|---|---|---|---|
| Small, portable | 1–2.2 kW | inverter, single-phase, 20–25 kg | fridge, freezer, router, lighting, charging; quiet, pure sine |
| Medium | 3–4 kW | inverter or open frame, single-phase | plus boiler with controls, small pumps |
| Large, wheeled | 5–8 kW | open frame, single- or three-phase, often electric start | household with well pump, part of the house via changeover switch |
| Stationary | 10–20 kVA and more | diesel or gas, three-phase, auto-start with automatic transfer switch | whole house, small business |
| PTO generator | 20–60 kW | driven by the tractor’s power take-off (540 rpm), three-phase | farm with animals, milking, ventilation |
Inverter or conventional?
For a home or cabin with electronics, an inverter generator is the first choice: pure sine wave, stable voltage, quieter, and the engine throttles back at part load. An example of consumption: a common 2.2 kW inverter generator runs about 3.5 hours on its 3.6-litre tank at 1,600 W, i.e. roughly one litre per hour, and about eight hours at a quarter load. From about 5 kW and for three-phase loads, conventional generators are more common and cheaper. If electronics run from one, an online UPS in between protects them.
Fuel: quantity, storage, shelf life
- Work out what you need: at about 0.5–1 litre per hour, a small generator needs 12–24 litres for 24 hours of continuous running. If you only run it for a few hours at a time (to cool down the freezer, charge batteries, pump water), a fraction of that is enough.
- Storage: private individuals are subject to quantity limits for flammable liquids. Municipal fire and rescue service guidance gives a maximum of 25 litres of highly flammable liquid such as petrol in a garage or shed, roughly 100 litres in total without a permit, and only small containers inside the home. Ask your local räddningstjänst before storing larger amounts.
- Shelf life: ordinary petrol ages and can gum up carburettors. Alkylate petrol keeps much longer and burns cleaner. Diesel needs a winter grade. Use and replace fuel regularly.
Carbon monoxide: the biggest danger
A generator never runs inside the house, basement, garage, carport or shed, not even with the door open. The exhaust contains carbon monoxide (CO), an odourless gas that can knock you unconscious within minutes. According to the US Consumer Product Safety Commission, opening windows and doors is not enough. The US CDC recommends keeping generators at least about 6 metres (20 feet) from doors, windows and vents. In Sweden, a record number of people needed hospital care for CO poisoning in 2022, and a few people die from it every year. Place the generator outdoors with the exhaust pointing away from the house, and fit a CO alarm indoors. In winter, make sure snow does not block the exhaust.
Connection: three legal ways and one forbidden one
- Devices straight to the generator. An outdoor-rated extension lead with an adequate cross-section, fully unrolled, from the generator to the fridge. No work on the fixed wiring, possible straight away. Earth the generator as the manufacturer instructs.
- Inlet and changeover switch. An authorised electrician fits a changeover switch with grid–0–generator positions (mechanically interlocked so both can never be connected at once) and an inlet on the outside wall, usually CEE. Ideally the switch only feeds selected circuits (a backup sub-board): heating, water, fridge and freezer, a few sockets and lights. The electrician notifies the network operator and decides how earthing and residual current protection work in generator mode.
- Automatic transfer switch (ATS) with auto-start. For stationary generators. When the grid fails, the generator starts by itself and takes over after a few seconds. Worthwhile when nobody is on site: a cabin in winter, a farm with animals, a business.
Forbidden and potentially lethal: feeding the generator into the house wiring through a wall socket (a so-called suicide cable with a plug on both ends). The current then also flows back into the public grid and, through the transformer, up to the medium-voltage side. Line workers who believe the line is dead can be killed. On top of that you risk fire, destroyed appliances and, when grid power returns, a destroyed generator. The Swedish energy industry explicitly requires a standby generator to be connected only to a de-energised customer installation.
Home battery: island mode or grid-tied only?
This is the biggest misunderstanding in the whole topic. Many people think: I have a battery in the basement, so I have backup power. Often that is not true.
Grid-tied: the normal case
A grid-tied battery works with the grid: it charges from solar or cheap grid power and supplies the house when that pays off. When the grid fails, every grid-tied inverter has to shut down within a fraction of a second. That is a requirement, so that no installation feeds a line someone is working on. Without extra equipment the house goes dark, even though the battery and solar panels could deliver.
Island mode (backup): with extra equipment
For a battery to keep delivering during an outage, the house must be disconnected from the grid and the inverter must be able to form a grid of its own. Manufacturers solve this in different ways, and the terminology is inconsistent:
| Manufacturer / system | What is needed for backup | Switchover, power |
|---|---|---|
| Huawei SUN2000 with LUNA2000 | Backup Box B0 (single-phase) or B1 (three-phase) | retailers quote about 3 s switchover, power depends on the box |
| SolarEdge | Home Backup Interface (single- or three-phase) | grid disconnection under 100 ms according to the datasheet |
| Fronius Symo GEN24 “PV Point” | nothing extra, but only one single-phase socket | 3,000 VA, only while the sun shines, up to 15 s switchover |
| Fronius Symo GEN24 “Full Backup” | battery plus transfer equipment; not available on the smallest models | whole household |
| Tesla Powerwall 3 | Gateway or Backup Switch | 11.5 kW continuous per unit, starts motors up to 185 A locked rotor current (LRA) |
The table shows examples, not recommendations. What matters is the pattern: with almost every system, backup is an option you have to order, install and configure explicitly. Retrofitting is often possible, but costs electrician time and sometimes a different inverter.
Partial backup, whole-home backup, backup socket
- Backup socket: a socket on the inverter that supplies power during an outage. Good for a fridge and router via extension lead.
- Partial backup: selected circuits are on a backup sub-board. The usual and generally the most sensible approach.
- Whole-home backup: the entire house. Sounds convenient, but then the sauna, cooker, car charger and immersion heater are connected too. Without load management the battery is flat in no time or the inverter is overloaded.
Single-phase or three-phase?
Swedish houses have a three-phase supply. Many backup solutions only provide one phase in island mode, or they are limited per phase (phase imbalance). A three-phase motor, for example in an older heat pump, will not run on one phase. Ask for the power per phase in island mode.
Questions for the installer before you sign
- Does the system supply power during a grid outage, and what extra hardware does that require? Is it included in the quote?
- How long is the switchover? Will computers and heating controls notice?
- How much power is available in island mode, in total and per phase? What starting current can it handle?
- Can it start from empty without the grid (black start), for example in the morning on solar?
- Does the battery keep charging from the panels in island mode? Can I connect a generator to recharge it?
- What happens if only one phase of the grid fails?
- Can I set a reserve that the price optimisation will not touch?
- How high is the idle consumption, in grid mode and in island mode?
- Will I get a notification on my phone when the grid is down, and how long the battery will last?
Green technology deduction only with solar
Batteries only qualify for the green technology tax reduction (grön teknik: 50 % of labour and materials, up to SEK 50,000 per person per year) if they are connected to grid-tied self-generation and store electricity you produce yourself. A battery purely for backup and price optimisation, without solar panels, gets no deduction.
The trade-off: saving money or keeping a reserve
A battery that is emptied every evening to save on electricity prices is no help in a power cut at midnight. If you want both, you need a fixed reserve that the optimisation leaves alone, and you have to accept that this part of the battery saves nothing.
From my own installation
In Stöde I run a three-phase 15 kW hybrid inverter with a large battery, controlled through Home Assistant and my own software. I do not have solar panels yet; the battery charges from the grid during cheap quarter-hours. What that saves is described in the case study with 69 days of measurements. For backup power, other lessons matter more:
- The inverter comes from the off-grid world. When the grid goes, it keeps supplying the house from the battery, including the fibre router, which is deliberately connected to its output. The price is high self-consumption: about 126 W, around the clock (my own measurement) – it is fairly power-hungry. Branded home battery systems are considerably more frugal; for customer calculations I assume about 15 W including the battery management system (BMS).
- The reserve comes before savings. By design the battery does not go below roughly half. Below that there is a hard floor of 30 % that the control system defends regardless of price.
- It pre-charges before storms and cold. If SMHI issues a yellow or higher warning for wind, snow or rain for my location, or the forecast shows −20 °C or colder on any of the next few days, the control system charges fully even at higher prices.
- A partial outage is a full outage. If just one of the three phases fails – the cause can be the grid or your own main fuse – my inverter goes into fault mode and draws nothing at all from the grid. That is why the control system monitors each phase separately and treats the loss of one phase as a total outage.
- The key number is range, not state of charge. When the grid fails I get a phone notification with the affected phases, the current house load and the estimated range: usable energy down to the reserve divided by the current load. “Battery 70 %” tells you little in an emergency; “lasts another 14 hours at current load” tells you everything.
- When the power goes, the internet often goes too. So the system queues notifications and delivers them as soon as the connection is back.
- The main fuse limits recharging. With a 20 A main fuse, the control system limits the charging power so the fuse does not trip. After a long outage the battery is therefore not full again within an hour.
My takeaway: backup power is not a feature of a device but an operating mode that you have to plan, configure and monitor deliberately.
All options compared
| UPS | Power station | EV (V2L) | Inverter generator | Fixed generator + switch | Home battery with island mode | |
|---|---|---|---|---|---|---|
| Switchover | 0–20 ms | manual or under 10–30 ms | manual | manual | manual or automatic (seconds) | milliseconds to seconds |
| Power | 0.3–3 kW | 0.3–3.6 kW | up to about 3.6 kW | 1–4 kW | 5–20 kW and more | 3–12 kW depending on system |
| Duration | minutes to hours | hours to 1 day | 1 day or more | as long as fuel lasts | as long as fuel lasts | hours to days, longer with solar |
| Voltage quality | depends on type | pure sine (good models) | pure sine | pure sine | depends on generator | pure sine |
| Noise, exhaust | no | no | no | yes, moderate | yes | no |
| Electrician needed | no | no (only for a transfer panel) | no (V2H: yes) | no (for a switch: yes) | yes | yes |
| Maintenance | battery every few years | charge, test | none extra | test runs, oil, fuel | test runs, servicing | software, test |
Decision tree by scenario
The three basic questions
- Must there be no interruption at all? Yes → UPS (or a home battery with a very short switchover) for exactly those devices, whatever else you choose.
- Is one day enough? Yes → power station, EV with V2L, or home battery with island mode. No → add a way to recharge: generator or solar.
- Do you need more than 3–4 kW, three phases or large motors? Yes → fixed generator with changeover switch, or a three-phase home battery with whole-home backup, both with an electrician. No → portable solutions will do.
Detached house with a heat pump
Running the heat pump itself in backup mode is rarely realistic, and certainly not with the immersion heater. What is realistic: a wood stove for heat, a UPS for the router and heating controls, a power station or small inverter generator for the fridge, freezer and water. If you want more, have a backup sub-board with a changeover switch installed and run heating controls, circulation pump, fridge, freezer and well pump from a generator of around 5 kW or more. If you are planning a battery anyway, choose island mode and three phases from the start, and agree with the installer whether the heat pump may and should start in island mode.
Terraced house or district heating
District heating also needs electricity: the substation in the house has pumps and controls. For outages of a few hours, a UPS for the network and a power station for fridge and lights are enough. A generator is often impractical in a terraced house because of exhaust, noise and neighbours.
Cabin that is not lived in year-round
Here it is less about comfort and more about damage: frost, frozen pipes, cameras going offline. What matters is a router and sensors with long runtime (UPS or power station with 12 V output), a notification on power loss and on temperatures below +5 °C, and a plan for who drives out during a long outage. If someone is on site, a small inverter generator covers fridge, freezer, water pump and charging. An auto-start generator for an empty cabin is possible, but needs a permanently installed changeover switch, a safe location and remote monitoring. More on remote monitoring: holiday home in Sweden: monitoring and internet.
Off-grid
Without a grid connection the battery is not backup, it is the system. The emergency here means long dark weeks in December, snow on the panels, a broken inverter. A generator to recharge the battery is practically always part of the setup, and critical loads (cameras, router, frost protection) should have priority. A real example from the region: the off-grid cabin case study.
Farm with animals
Here backup power is not a matter of comfort. Under the EU directive on the protection of farmed animals (98/58/EC), which also applies in Sweden, buildings with artificial ventilation must have an appropriate backup system that guarantees sufficient air renewal if the system fails, plus an alarm that warns of breakdowns and is tested regularly. Automated equipment essential to the animals must be inspected daily. Insurers also set requirements for alarms and standby generators on farms. Typical solution: a PTO generator for the tractor or a stationary diesel generator, three-phase, through a permanently installed changeover switch, plus an SMS or app alarm that works independently of the grid. Be honest about the starting power of vacuum pumps, milk cooling, fans and feeding motors, and remember drinking water. For Wi-Fi and cameras in the barn, see Wi-Fi and cameras on the farm.
Small business
A UPS for server, network and till, with automatic shutdown when the batteries run low. For refrigeration (food, medicines) or production, a generator with a changeover switch, often with auto-start. Plus a written plan: who switches over, where is the key, who informs customers?
Winter in Norrland
- Cold and batteries: do not charge lithium batteries below 0 °C; store them frost-free. In an emergency, bring the power station into the warmest room.
- Cold and generators: use winter oil as the manufacturer specifies, keep the starter battery charged, and practise cold starts in advance. Winter diesel, not last year’s summer diesel.
- Snow and ice: put the generator under a roof but in the open. Snow in front of the exhaust can push fumes towards the house. Keep the path to the generator clear, at night as well.
- Storms and ice loading: outages from fallen trees and iced-up lines last longest, because crews first have to reach the damage. That is when tier 3 counts.
- Heat without electricity: at −20 °C a house cools down, depending on insulation, within hours to a few days to the point where pipes are at risk. A wood stove and firewood are part of every backup plan.
Costs at market prices
Prices as of October 2026 from Swedish shops and price comparison sites, including VAT. They vary widely and are not recommendations of particular models.
| Solution | Example | Price SEK |
|---|---|---|
| Line-interactive UPS | 750 VA | from about 1,300 |
| Online UPS | 1,000 VA | about 6,000–11,000 (converted from Danish and Norwegian price comparisons) |
| Power station | 1,024 Wh LFP, 1,800 W | about 8,800 |
| Inverter generator | 3.5 kW, budget brand to branded | about 7,000–12,500 |
| Inverter generator | 2.2 kW, branded | about 16,600 |
| Inverter generator | 6.5 kW | about 11,500 |
| PTO generator | 30 kW, three-phase | about 44,000–64,000 |
| Home battery | 10 kWh installed, before deduction | about 85,000–110,000, backup equipment extra depending on system |
| Changeover switch, inlet, backup sub-board | electrician’s work | by quote; depends heavily on the consumer unit |
For comparison: with SEK 8,000 in annual network charges, a 36-hour outage brings SEK 3,000 in compensation. Backup power rarely pays off in money, but in damage avoided and peace of mind.
Fixed-price packages
- Check plus Power cut – SEK 2,500. About 2.5 hours on site: inventory and measurement of critical loads, runtime calculation, mobile coverage, priority plan, specification for the electrician and a test plan.
- Setup Backup power monitoring – SEK 3,500 plus hardware. For an existing home battery: outage detection per phase, phone notification with estimated range, pre-charge rules for storms and cold.
Private customers pay including VAT, businesses and farms excluding VAT. Travel within Medelpad is included. The price of a check is credited if you then order a setup. The RUT deduction applies to work on routers, networks and computers – shown separately on the invoice – but not to alarms, cameras, smart home or remote support. Work on the fixed house wiring is done by an authorised electrician.
Rules in Sweden
- Work on the fixed wiring (changeover switch, inlet, backup sub-board, backup box) may only be carried out by an electrical installation company with an authorised electrician. The rules come from the Swedish National Electrical Safety Board (Elsäkerhetsverket).
- Prevent backfeeding: a generator is only connected to an installation that is disconnected from the grid and de-energised. The changeover switch has to guarantee this mechanically.
- Inform the network operator: the electrician notifies the work. Batteries and solar systems are generating installations and must be registered with the network operator anyway. Operators have their own technical conditions, for example a permanently installed, lockable isolator.
- Do not tinker during a power cut: Elsäkerhetsverket points out that power can return at any moment without warning. Never touch fallen lines.
- Carbon monoxide: generators outdoors only. CO alarm indoors.
- Fuel storage: follow the räddningstjänst quantity limits.
- Animals: backup system and alarm for artificial ventilation (Directive 98/58/EC); check your insurer’s requirements.
- Compensation: avbrottsersättning from 12 hours, damages possible on top. From 2027, the Electricity Market Act.
Maintenance: making sure it works when needed
UPS
- Use the self-test function, or pull the mains plug every six months and time how long it lasts.
- Replace lead-acid batteries as the manufacturer recommends, typically after a few years. A swollen battery must come out immediately.
Power station
- Check and top up every three months. Many manufacturers recommend storing at around 60–80 % charge, and full before winter.
- Once a year, run a real test with the planned load (the fridge) for a few hours.
Generator
- Start it every month and let it run for at least 20–30 minutes under load, not idling.
- Change the oil by running hours or annually; check the spark plug and air filter.
- Rotate fuel or use alkylate petrol, and run the carburettor dry before longer storage (per manufacturer).
- Try the changeover switch with the generator once a year, exactly as you would in an emergency.
Home battery
- Check the reserve setting after every software update.
- Test island mode once a year the way your installer showed you: which circuits work, for how long, does the phone notification arrive?
For all of them
- A laminated quick guide at the consumer unit or generator: the steps in order, which circuits work, where the cable is.
- A torch with fresh batteries in a fixed place, so you can read the guide in the dark.
Common mistakes
- Bought a battery, assumed backup. Without a backup box or transfer equipment, the lights stay off.
- Reserve set to 0 %. Price optimisation has emptied the battery, and that is exactly when the power fails.
- Generator chosen by running power. The well pump will not start.
- Generator in the garage “with the door open”. Risk of death from carbon monoxide.
- Feeding in through a socket. Forbidden and potentially lethal, for others and for yourself.
- Last year’s petrol. The generator will not start when you need it.
- A flat power station in the cupboard. Without regular charging it is useless in an emergency.
- Router not backed up. There is power, but no connection and no notifications.
- Forgetting the heating. Pellet, oil and district heating also need electricity.
- Car charger on the backup circuit. The car drains the home battery within an hour.
- No test. The first attempt happens in the dark at −25 °C.
Printable checklist
Backup power planning in ten steps
- List: what must run during an outage? (heating, water, refrigeration, communications, lighting, animals, business)
- For each device: watts, starting current (rating plate), kWh per day, can it tolerate a short interruption?
- Total running load + largest start-up + 20–25 % margin = power needed
- kWh per day × planned days + idle consumption = energy needed
- Devices that must not be interrupted → UPS
- Up to one day → power station, EV, home battery with island mode
- Several days → plan recharging: generator, solar, fuel reserve
- Decide on connection: extension lead, or changeover switch by an authorised electrician
- Safety: generator outdoors, CO alarm, fuel stored according to the rules
- Test, document, repeat every year
Frequently asked questions
Can I feed a generator into my house through a socket?
No. A lead with a plug on both ends is forbidden and potentially lethal: power can flow back into the public grid and kill line workers, and the pins of the loose plug are live. The only legal way into the house wiring is a grid–0–generator changeover switch fitted by an authorised electrician. Without a switch, run devices directly from the generator with extension leads.
Will my home battery automatically supply power during a power cut?
Usually not. Grid-tied inverters must shut down when the grid fails. You only get backup power with the right additional equipment, such as a backup box or transfer equipment, and if the function is installed and configured. Ask your installer specifically about island mode, power per phase and switchover time.
How big a generator does a house need?
Add up the running load of everything that should run at once, plus the largest starting current (often the well pump), plus a 20–25 % margin. For heating controls, fridge, freezer, well pump and lighting, many households end up at around 4–6 kW. A heat pump with its immersion heater needs far more and is usually not run in backup mode.
How long does a 1 kWh power station last?
With a fridge, a 4G router, two cameras and some lighting, about one night; without the fridge, nearly a day. Inverter losses and idle consumption are decisive. Running devices from the 12 V outputs extends runtime.
Which UPS do I need for my router and fibre box?
A line-interactive UPS of around 700–1,000 VA runs a router, fibre box and switch for several hours. An online UPS is worth it for sensitive equipment or behind a conventional generator.
Can I leave a power station in the cabin over winter?
You can store it there, but frost-free is better. Lithium batteries must not be charged below 0 °C, and usable capacity drops in the cold. Charge it before winter and check it regularly.
Will the network operator pay me if the power is off for a long time?
Yes, automatically from 12 hours of continuous outage: 12.5 % of annual network charges for 12–24 hours (at least about SEK 1,200 in 2026), a further 25 % for each additional 24-hour period started, up to 300 %. This reflects the Electricity Act as of October 2026; from 2027 the new Electricity Market Act applies.
Is there a green technology deduction for a backup-only battery?
No. According to Skatteverket, the 50 % reduction only applies if the battery is connected to grid-tied self-generation such as solar panels and stores electricity you produce yourself.
Do you install the changeover switch or backup box?
No. Work on the fixed wiring is done by an authorised electrician. I work out your requirements, compare the options, review quotes and, if you like, set up monitoring and control, for example a notification on power loss and a range display in Home Assistant.
No affiliate links. Recommendations are based purely on hands-on experience.
Want to know which backup power solution suits your house, cabin or farm? My Check plus Power cut at a fixed price of SEK 2,500 (private customers incl. VAT, travel within Medelpad included): I survey the important loads (rating plates, measurements), work out power, starting current and runtime, compare two suitable solutions with a cost range and write up the specification for your electrician. If you wish, I can then set up a phone notification on power loss with the estimated range in the Setup Backup power monitoring (SEK 3,500 plus hardware, check credited). In English, Swedish or German, reply within 24 hours.
Energy & control: get in touch Book a free callExternal sources:
- Electricity Act (1997:857): ch. 4 s. 20 (24-hour rule), ch. 10 ss. 10–12 (outage compensation)
- Act (2026:1282) introducing the Electricity Market Act – replaces the Electricity Act from 2027
- Network operator notice on outage compensation 2026 (minimum amount)
- Energy Markets Inspectorate: Supply reliability in Sweden’s grids 2024 (Ei R2025:17)
- SVT: Storm Gudrun changed the grid for ever
- Swedish Energy Agency: Supply security – experience from Sweden (Gudrun: 730,000 customers, 45 days)
- Elsäkerhetsverket: During a power cut
- Umeå Energi Elnät: backup power notification form (example from a grid operator)
- Vattenfall Eldistribution: Technical conditions for own generation 2026
- US CPSC: What to know about generators (CO)
- US CDC: Avoiding carbon monoxide poisoning
- Swedish Poisons Information Centre: record CO poisonings in 2022
- UPS topologies and transfer times (IEC 62040-3)
- Schneider Electric White Paper 1: The different types of UPS systems
- Fronius Symo GEN24: PV Point and Full Backup
- SolarEdge Backup Interface datasheet
- Huawei FusionSolar catalogue 2023 (Backup Box B0, switchover under 3 s)
- Tesla Powerwall 3 datasheet
- Skatteverket: Green technology – approved work
- Directive 98/58/EC, Annex point 13 (artificial ventilation: backup system and alarm)
- REDARC: do not charge lithium batteries below 0 °C
- Generator sizing guide: running and starting watts
- NIBE F1255 datasheet (immersion heater)
- Fire and rescue service: flammable liquids at home and in leisure
- CAR Magazine: vehicle-to-load in practice
- Market price, 2.2 kW inverter generator (Bygghemma)
- PriceRunner: inverter generators
- PriceRunner: 1,024 Wh power station
- Market price, 30 kW PTO generator (Bygghemma)
- Market price, 750 VA UPS (Inet)
- Boio: solar and batteries 2026, prices and deductions